BEEHE in-row L2L CDUs transfer heat from secondary server coolant to a primary facility water circuit. They are suited to liquid cooling deployments that serve multiple racks from a shared distribution unit.
Key features
- N+1 variable-speed pumps and pressure/flow control support the secondary coolant circuit.
- A 10-inch PLC interface displays coolant temperature, pressure, flow, level and leak status.
- Top or bottom piping arrangements, automatic refill and anti-condensation functions support different installation layouts.
- Dual power inputs and Modbus RTU/TCP, SNMP and Redfish interfaces are listed.
- Group control supports up to 12 units.
Configurations and specifications
| Model | Listed cooling capacity | Secondary flow | ATD |
|---|---|---|---|
| IB300 | 300 kW | 420 L/min | 5°C |
| IB600 | 600 kW | 900 L/min | 5°C |
| IB1350 | 1,350 kW | 1,440 L/min | 4°C |
| IB1350P | 1,350 kW | 1,800 L/min | 4°C |
| IB1800 | 1,800 kW | 2,400 L/min | 4°C |
| IB2000 | 2,000 kW | 1,893 L/min | 3°C |
| IB2300 | 2,300 kW | 3,450 L/min | 4°C |
Application and selection
ATD is the difference between secondary outlet temperature and primary supply temperature. Capacities above apply at the listed ATD and must be checked against project water temperatures, flow and pressure requirements. Select the coolant, piping orientation and electrical configuration for the installation.
Brand: BEEHE. Admetal is an official distributor of BEEHE products.